RCF MX 3250/2

The RCF MX 3250/2 is a 2 chnnel voice evacuation master unit from the DXT 3000 system, fully EN54 compliant.

Ideal for a small to medium size application where an EN54-16:2008 system is required.

The digital DSP-based master unit is equipped with 2 RCF Class D+ power amplifiers. The total maximum output power (sum of all zones) is 250 W and is freely assignable accross the zones.

Amplifier outputs are for 100 V / 70 V constant voltage speaker lines. Each zone has two outputs (to get redundant lines). 

Thanks to its internal digital matrix, each power amplifier can send to its zone a different signal (among all the available, e.g. emergency / routine announcements, pre-recorded messages, background music).

The second amplifier channel can alternatively be used as spare (with automatic change-over) in case of a fault.

The MX3250/2 has an integral backup power supply that meets the EN 54-24 standard, with recharging unit and the necessary EN54-4 circuitry for the DC back-up and check of batteries. (see AC BAT 18)

Furthermore it offers inputs, controls and pre-recorded messages to get a real plug & play solution.

The system can be completed with monitored paging consoles BM 3804 and 6 button extensions BE 3806, allow to complete the installation by adding live announcements. Local single-button paging consoles (not monitored) BM 3022 and background music programs can be implemented as well.

DXT 3000 system has been designed to be wired by using very convenient fire-rated J-TYPE cables for paging console and interlink connections.

  • Equipped with 2 RCF Class D+ technology power amplifiers
  • Internal power supply with battery charger and space for batteries
  • An audio input for a line made of up to four monitored BM 3804 paging microphones for selective announcements (linked in ‘daisy-chain’, with or without additional BE 3806 keyboards, according to the max. number of zones).
  • An audio input for a line made of one or more BM 3022 paging microphones (not monitored and linked in ‘daisy-chain’) for general calls only.
  • An audio input for a background music source (i.e. MP3 / CD players, tuners, etc.).
  • Logic inputs and outputs to interface to the fire alarm system (or others). 
  • An internal player of pre-recorded messages stored on monitored SD CARD. 
100V Evac multi-ch multi-zn
List Ex VAT: £2,458.00
Log in for Trade Prices
CONTACT US

SPECIFICATIONS

Max. overall output power: up to 250 W, freely assignable to the 2 zones
Frequency response: 20 Hz ÷ 20 kHz (± 1 dB)
Distortion (THD + N): < 0.3% (@ 1 kHz)
Output voltage to speaker lines: 100 V / 70 V
Signal / noise ratio: > 90 dBA
Operating voltage (mains): 230 / 115 V ac (50 / 60 Hz), internal setting
Operating voltage (batteries): 24 V dc
Input connectors: removable screw terminals
Max. number of daisy-chained BM 3804 paging microphones: 4
Simultaneous audio channels: 3
Paging microphone cable: CAT 6 FTP or J-type (RCF)
Dimensions (w x h x d): 430 mm x 530 mm x 180 mm (19" rack – 12 units)

Related Products

RCF BM 3804

Monitored & pre-amplified desktop paging microphone for RCF DXT 3000 voice evacuation system. EN54 compliant.

see more
List Ex VAT: £593.00
RCF BATT 18AH 2X

Pair of batteries for RCF MX 3250 controller, part of the DXT3000 voice evacuation system. EN54-24 compliant.

see more
List Ex VAT: £136.00
RCF EOL 3-9

End of line termination for RCF Voice Evacuation System

see more
List Ex VAT: £59.00